IP67 vs IP68 Electric Actuator: What Buried Pits and Wash-Down Bays Actually Need

IP67 vs IP68 Electric Actuator: What Buried Pits and Wash-Down Bays Actually Need

2026-11-23

IP67 vs IP68 Electric Actuator: What Buried Pits and Wash-Down Bays Actually Need

A flooded valve pit rarely takes an actuator offline because the nameplate says IP67. It happens because water found a path the rating never described: a cable gland tightened by hand, a cover gasket that took a permanent set after two summers, or an actuator mounted face-up where condensate collects, freezes and prises the seal open. Most buyers reach this topic by searching for an IP68 electric actuator for buried service, then discover that the certificate describes a laboratory immersion rather than their pit. SONGO supplies the same valve platform in IP65, IP67 and IP68 enclosures, and the more useful question is not which number is higher, but where the water actually enters.

What IP67 and IP68 actually prove

Both ratings carry a first digit of 6, which means dust-tight. The difference sits entirely in the second digit, and it is narrower than most catalogue pages suggest.

IP67 qualifies short-term immersion: one metre for thirty minutes under stated conditions, with no harmful ingress. That covers rain, hose-down, splash, and a pit that drains.

IP68 qualifies continuous immersion at a depth and duration declared by the manufacturer. There is no single IP68 test. One supplier may declare 1.5 m for 24 hours, another 10 m for 72 hours. The certificate, not the badge, is the specification.

Rating Water condition qualified What it does not tell you
IP66 Powerful jet spray from any direction Nothing about immersion
IP67 1 m depth for 30 minutes Nothing about sustained pressure
IP68 Continuous immersion; depth and duration declared by the maker Nothing about your gland, gasket or mounting
IP67 and IP68 electric actuator enclosures compared: short-term immersion versus continuous underwater operation
IP67 covers short-term immersion; IP68 is the depth and duration the manufacturer declares. The certificate, not the badge, is the specification.

The three paths water actually uses

1. Cable entry

The gland is the most common field failure and the least documented item on a datasheet. A gland that is hand-tightened, or fitted with the wrong insert for the cable diameter, leaves a capillary path straight into the terminal compartment. Specify gland type, cable diameter range and tightening torque on the commissioning sheet, not only in the manual.

2. Cover seal

Compression set is a time-and-temperature problem. A gasket that seals at 20 °C in the workshop may not seal after a year of 60 °C summer ambient and daily cycling. Keep the gasket part number in the spare-parts list; a seal that cannot be replaced on site is a single-use seal.

3. Mounting orientation

An actuator mounted with the terminal box facing up collects condensate, and a heater alone will not save a pocket of water sitting on a gasket. Where geometry allows, mount with the cable entry pointing down and add a heater with a thermostat for any location where the daily temperature swing crosses the dew point.

Where the enclosure ends and the valve begins

An ingress rating says nothing about whether the actuator can move the valve. In submerged or flood-prone pits the load is often higher than expected: a DN100 PN16 motorized ball valve may need roughly 240 N·m of breakaway torque once the seat has been in service, and a cold, wet gear train does not become more efficient with age. Two practical consequences follow. Size the actuator output against breakaway torque with a safety factor rather than against running torque, and prefer 24 VDC in pits where a technician may be standing in water, while 220 VAC remains common on above-grade skids.

This is also where an IP68 electric actuator is often bought to solve a drainage problem it cannot solve. If the pit fills because the sump pump is undersized, the correct fix is the pump. The rating only decides how long the actuator tolerates the consequences.

Parameter example: a flood-prone pit, DN80 line

  • Enclosure: IP68, declared condition 10 m for 72 hours, heater and thermostat fitted
  • Actuator: 24 VDC, 90° quarter-turn, 50 N·m output 
  • Valve: DN100, PN16, CF8M body, EPDM seat, wafer butterfly valve
  • Cable entry: M20 gland, 8–12 mm cable, torque recorded at commissioning
  • Ambient: -20 °C to +70 °C, anti-condensation heater active below dew point
SONGO IP68 electric actuator on a DN100 quarter-turn valve for buried pit and wash-down service
50Nm quarter-turn assembly with a SONGO electric actuator. Enclosure class, gland torque and mounting orientation decide the field outcome.

Match the rating to the water exposure class

Selection becomes simple once the question changes from "which rating is better" to "how does this location get wet".

Installation Real exposure Appropriate class What to verify
Above-grade skid, monsoon climate Rain, splash, occasional hose IP67 Gland torque, heater where cycling occurs
Wash-down bay, daily cleaning High-pressure jet and run-off IP67 minimum; IP68 if the jet is aimed at the cover Stainless housing, jet direction
Buried pit with working drainage Occasional standing water IP67 Drain maintenance is part of the design
Buried pit without drainage Periodic full immersion IP68 24 VDC, sealed gland, declared depth
Coastal platform or jetty Wave splash plus chloride IP68 with corrosion-resistant housing Rinse schedule, coating condition
Tank interior or wet well Continuous immersion IP68 Declared depth must exceed installed depth

How buyers actually search this

Query language is a useful signal of what the buyer is worried about, and it is worth writing for directly rather than paraphrasing into jargon.

  • "IP68 electric actuator for buried valve pit" — the buyer already assumes immersion and wants confirmation of depth and cable entry.
  • "washdown duty valve actuator" — food, beverage and pharma buyers usually mean daily chemical wash plus jet, not immersion; housing material matters as much as the rating.
  • "submersible electric actuator 24 VDC" — safety-driven, often retrofitting a pit where 220 VAC is no longer acceptable.
  • "IP67 or IP68 which one do I need" — an early-stage researcher who needs a decision rule, not a product page.
  • "actuator leaking water at cable gland" — a post-failure search; the answer that earns trust is the torque figure and the gasket part number.

If the pit drains and the jet is not aimed at the seal, an IP67 unit with a correctly made-off gland will usually outlast an IP68 unit installed carelessly. That sentence is the decision rule most buyers are looking for.

Commissioning: five steps that decide the outcome

Step 1 — Classify by water exposure. Rain, jet or immersion. Buy for the classification, not for the worst case in the catalogue.

Step 2 — Write the cable entry into the instruction. Gland type, cable diameter range and tightening torque, recorded on the commissioning sheet.

Step 3 — Fit a heater where cycling occurs. Any actuator that sees daily temperature swings across the dew point needs one, whatever its IP rating.

Step 4 — Record the declared IP68 condition. Depth and duration, in the project file. "IP68" without a test condition is a marketing claim.

Step 5 — Put the gland and gasket on the spare-parts list. Both are wear items, and both decide whether the rating survives year three.

Questions buyers ask before ordering

Is an IP68 electric actuator always better than IP67? No. It costs more and is justified only where immersion is expected. Above grade, the extra sealing does not compensate for a poorly made-off gland.

Can an IP67 unit be upgraded to IP68 later? Rarely. Seals, housing joints and cable entry are designed as one system; field upgrades usually address the symptom rather than the enclosure.

Does IP68 include corrosion protection? No. Ingress protection and corrosion resistance are separate specifications. Coastal and chlorinated environments need both, and salt spray is not covered by the IP code.

What does IP68 mean without a stated depth? It means the depth and duration are declared by the manufacturer. Ask for the test condition in writing before comparing quotations.

Summary

An ingress rating is a ceiling, not a guarantee. The gland, the gasket, the mounting orientation and the heater decide what the site actually receives. Buy for the water exposure class, write the declared IP68 condition into the project file, and size the actuator against breakaway torque rather than running torque. SONGO builds motorized ball valves and electric actuators in IP65, IP67 and IP68 configurations, with enclosure class, voltage and output torque matched to the installation instead of to a catalogue page.