A flooded valve pit rarely takes an actuator offline because the nameplate says IP67. It happens because water found a path the rating never described: a cable gland tightened by hand, a cover gasket that took a permanent set after two summers, or an actuator mounted face-up where condensate collects, freezes and prises the seal open. Most buyers reach this topic by searching for an IP68 electric actuator for buried service, then discover that the certificate describes a laboratory immersion rather than their pit. SONGO supplies the same valve platform in IP65, IP67 and IP68 enclosures, and the more useful question is not which number is higher, but where the water actually enters.
Both ratings carry a first digit of 6, which means dust-tight. The difference sits entirely in the second digit, and it is narrower than most catalogue pages suggest.
IP67 qualifies short-term immersion: one metre for thirty minutes under stated conditions, with no harmful ingress. That covers rain, hose-down, splash, and a pit that drains.
IP68 qualifies continuous immersion at a depth and duration declared by the manufacturer. There is no single IP68 test. One supplier may declare 1.5 m for 24 hours, another 10 m for 72 hours. The certificate, not the badge, is the specification.
| Rating | Water condition qualified | What it does not tell you |
|---|---|---|
| IP66 | Powerful jet spray from any direction | Nothing about immersion |
| IP67 | 1 m depth for 30 minutes | Nothing about sustained pressure |
| IP68 | Continuous immersion; depth and duration declared by the maker | Nothing about your gland, gasket or mounting |
The gland is the most common field failure and the least documented item on a datasheet. A gland that is hand-tightened, or fitted with the wrong insert for the cable diameter, leaves a capillary path straight into the terminal compartment. Specify gland type, cable diameter range and tightening torque on the commissioning sheet, not only in the manual.
Compression set is a time-and-temperature problem. A gasket that seals at 20 °C in the workshop may not seal after a year of 60 °C summer ambient and daily cycling. Keep the gasket part number in the spare-parts list; a seal that cannot be replaced on site is a single-use seal.
An actuator mounted with the terminal box facing up collects condensate, and a heater alone will not save a pocket of water sitting on a gasket. Where geometry allows, mount with the cable entry pointing down and add a heater with a thermostat for any location where the daily temperature swing crosses the dew point.
An ingress rating says nothing about whether the actuator can move the valve. In submerged or flood-prone pits the load is often higher than expected: a DN100 PN16 motorized ball valve may need roughly 240 N·m of breakaway torque once the seat has been in service, and a cold, wet gear train does not become more efficient with age. Two practical consequences follow. Size the actuator output against breakaway torque with a safety factor rather than against running torque, and prefer 24 VDC in pits where a technician may be standing in water, while 220 VAC remains common on above-grade skids.
This is also where an IP68 electric actuator is often bought to solve a drainage problem it cannot solve. If the pit fills because the sump pump is undersized, the correct fix is the pump. The rating only decides how long the actuator tolerates the consequences.
Selection becomes simple once the question changes from "which rating is better" to "how does this location get wet".
| Installation | Real exposure | Appropriate class | What to verify |
|---|---|---|---|
| Above-grade skid, monsoon climate | Rain, splash, occasional hose | IP67 | Gland torque, heater where cycling occurs |
| Wash-down bay, daily cleaning | High-pressure jet and run-off | IP67 minimum; IP68 if the jet is aimed at the cover | Stainless housing, jet direction |
| Buried pit with working drainage | Occasional standing water | IP67 | Drain maintenance is part of the design |
| Buried pit without drainage | Periodic full immersion | IP68 | 24 VDC, sealed gland, declared depth |
| Coastal platform or jetty | Wave splash plus chloride | IP68 with corrosion-resistant housing | Rinse schedule, coating condition |
| Tank interior or wet well | Continuous immersion | IP68 | Declared depth must exceed installed depth |
Query language is a useful signal of what the buyer is worried about, and it is worth writing for directly rather than paraphrasing into jargon.
If the pit drains and the jet is not aimed at the seal, an IP67 unit with a correctly made-off gland will usually outlast an IP68 unit installed carelessly. That sentence is the decision rule most buyers are looking for.
Step 1 — Classify by water exposure. Rain, jet or immersion. Buy for the classification, not for the worst case in the catalogue.
Step 2 — Write the cable entry into the instruction. Gland type, cable diameter range and tightening torque, recorded on the commissioning sheet.
Step 3 — Fit a heater where cycling occurs. Any actuator that sees daily temperature swings across the dew point needs one, whatever its IP rating.
Step 4 — Record the declared IP68 condition. Depth and duration, in the project file. "IP68" without a test condition is a marketing claim.
Step 5 — Put the gland and gasket on the spare-parts list. Both are wear items, and both decide whether the rating survives year three.
Is an IP68 electric actuator always better than IP67? No. It costs more and is justified only where immersion is expected. Above grade, the extra sealing does not compensate for a poorly made-off gland.
Can an IP67 unit be upgraded to IP68 later? Rarely. Seals, housing joints and cable entry are designed as one system; field upgrades usually address the symptom rather than the enclosure.
Does IP68 include corrosion protection? No. Ingress protection and corrosion resistance are separate specifications. Coastal and chlorinated environments need both, and salt spray is not covered by the IP code.
What does IP68 mean without a stated depth? It means the depth and duration are declared by the manufacturer. Ask for the test condition in writing before comparing quotations.
An ingress rating is a ceiling, not a guarantee. The gland, the gasket, the mounting orientation and the heater decide what the site actually receives. Buy for the water exposure class, write the declared IP68 condition into the project file, and size the actuator against breakaway torque rather than running torque. SONGO builds motorized ball valves and electric actuators in IP65, IP67 and IP68 configurations, with enclosure class, voltage and output torque matched to the installation instead of to a catalogue page.